Scalable Reference Electrical Architectures for Modern Data Centers
Listen
Radio episode about this paper
Transcript
Introduction to the show: ident: Robotics Radio. Generated commentary on the latest robotics and control papers.
Rosa: I'm Rosa.
Dev: And I'm Dev, here with Taro.
Rosa: We're looking at the paper: "Scalable Reference Electrical Architectures for Modern Data Centers".
Dev: Here's the gist of the paper. The paper presents scalable, vendor-neutral reference electrical architectures for modern data centers that bridge facility-level design with utility and grid planning.
Rosa: This framework integrates modular Power PODs, hierarchical distribution, standby generation, UPS systems, BESS, and utility interfaces into a unified methodology <ref:2611.15712#pg3>.
Dev: Core Framework Components The proposed framework represents the principal functional elements found in modern data-center electrical systems <ref:2611.15712#pg4>.
Rosa: These elements include the utility service interface, HV substations, HV/MV transformers, MV switchgear and feeders, modular power PODs, standby generators, automatic transfer switches (ATSs), uninterruptible power-supply (UPS) systems, battery energy-storage systems (BESSs), and low-voltage (LV) switchboards <ref:2611.15712#pg4>.
Title and authors: Rosa: So what’s the actual mechanism behind this scalable reference electrical architecture? They break it down into these components like utility service interfaces, HV substations, transformers, switchgear, and then those modular Power PODs >
Dev: And they bundle everything together—the UPS systems, battery energy storage systems or BESS, the standby generators with automatic transfer switches or ATSs—into one unified methodology for planning >
Rosa: It’s not just listing parts; it’s a way to organize them hierarchically. They separate the infrastructure into HV, MV, and LV layers so you have a consistent representation no matter how big the facility gets >
Dev: That hierarchical structure is key because it lets you maintain that planning representation over a wide range of facility sizes, which is what they call consistent capacity expansion and utility interconnection studies >
Rosa: And then they introduce this modular scaling methodology. It tells you to determine the number of Power PODs based on the target IT capacity and the specific IT capacity each POD can handle >
Dev: So it’s a formula for scaling things, using that relationship where N times q times N pod equals your total equipment quantity for a specific type of gear >
The paper's summary: Rosa: One improvement they point out is this PUE modeling. They explicitly separate the IT loads from the cooling and auxiliary loads within their architecture >
Dev: That’s important because AI and high-performance computing facilities are so tightly integrated where power and thermal infrastructure are inseparable, so being able to model that separation gives you flexibility in choosing cooling technologies against the power demands >
Rosa: They also mention how this framework allows for evaluating electrical infrastructure requirements, equipment demand, and future transmission and distribution planning associated with large-scale data center deployment >
Dev: That’s what makes it useful for utility studies. They show how you can use this reproducible benchmark to estimate the necessary utility interconnection requirements and look ahead at transmission and distribution planning >
Rosa: And they also tackle reactive power support. They say that STATCOM requirements can be determined independently based on the facility apparent-power capacity to represent planning-level equipment estimation for reactive power support at the grid interface >
The paper's improvements: Dev: So to wrap up, this paper proposes a scalable and vendor-neutral reference electrical architecture for data centers that uses modular Power PODs with hierarchical distribution to do facility design and grid planning all in one place >
Rosa: It gives operators a reproducible benchmark for estimating electrical infrastructure requirements, equipment demand, and future transmission and distribution planning when deploying large-scale data center deployments >
Dev: The real strength is the modular power POD methodology which allows for consistent capacity expansion based on predefined modular building blocks rather than bespoke designs >
Taro: When you look at it from a failure mode side, this structure helps define exactly how the system handles different levels of disturbance, like instantaneous ride-through versus longer-duration standby generation >
Rosa: And they’ve shown that by using these standardized topologies, we can get a consistent representation across everything from tens of megawatts to multi-gigawatt campuses >
Dev: It’s a solid framework for preliminary planning and it lets us test the impacts of large-scale data center deployment on future power systems in a structured way >
Conclusion: Rosa: So we’ve been looking at this paper, "Scalable Reference Electrical Architectures for Modern Data Centers," and basically, they’ve put together a method to take those massive data center designs and turn them into something you can actually use for planning utility grids >
Dev: Yeah. It's about creating a vendor-neutral reference architecture that bridges the gap between designing a specific facility on the ground and how the power grid needs to handle it upstream >
Rosa: The core thing they’re doing is using modular Power PODs as the basic building block for everything, from high voltage substations down to those low voltage switchboards >
Dev: Exactly. It’s not just listing equipment; they show you how to scale capacity consistently by figuring out how many of those PODs you need based on the target IT capacity and what each individual POD can handle >
Taro: I like that modular scaling idea, but it makes me wonder about the failure modes when that scaling hits a real-world unexpected event, like a sudden grid instability >
Rosa: Right. Because this framework lets you see how the infrastructure scales as you add more IT capacity and then it’s built to handle those predefined thresholds for things like transmission planning >
Dev: That’s the point. You get this reproducible benchmark for estimating equipment demand and utility interconnection requirements across many different data center sizes >
Taro: It really helps because it gives you a consistent starting point to test how well these designs perform when the world throws something weird at them, not just in a controlled simulation >
Rosa: So ultimately, this work provides a way to estimate the electrical infrastructure needed for these huge facilities and shows how they can adapt to different redundancy philosophies >
Dev: It’s a powerful tool for anyone doing utility planning or transmission studies because it takes complex facility characteristics and turns them into something you can actually model for the grid >
Taro: It gives you that baseline, that common representation, which is useful when you’re trying to figure out how much reactive power support those large facilities need from the grid >
Rosa: So yeah. The main thing here is this scalable and hierarchical way they put all the pieces together for electrical design >
Dev: It gives us a solid way to look at these massive deployments and understand what kind of infrastructure is actually required on the ground compared to what the utility needs to provide >
Taro: It’s a good tool for testing how those large-scale deployments interact with existing power systems, which is always where the real issues come up >
Argonne National Laboratory
eess.SY, cs.SY
Submitted: 2026-11-11
Updated: 2026-11-11
Comments: 5 pages, 3 figures, conference article
License: http://arxiv.org/licenses/nonexclusive-distrib/1.0/
Importance score: 87/100
The gist: The paper presents scalable, vendor-neutral reference electrical architectures for modern data centers that bridge facility-level design with utility and grid planning.
Key concepts
- Modular Power PODs
- These are the fundamental, repeatable building blocks of the electrical system. They encapsulate a standardized set of equipment—like transformers, generators, and UPS modules—allowing operators to scale capacity predictably by simply adding more PODs based on IT demand.
- Hierarchical Architecture
- The design organizes electrical infrastructure into distinct layers: High Voltage (HV), Medium Voltage (MV), and Low Voltage (LV). This structure ensures a consistent planning representation that remains valid regardless of the facility's size, from small to multi-gigawatt campuses.
- Modular Scaling Methodology
- Capacity expansion is managed by relating IT capacity to the number of required PODs (Nx = qxNpod). This methodology allows planners to determine how many PODs are needed based on target IT capacity and selected POD capacities, ensuring consistent scaling.
- Planning Application
- The framework translates facility characteristics into a complete electrical representation. This output is used for crucial tasks like estimating utility interconnection needs, calculating equipment demand, and conducting future transmission and distribution planning.
Terminology
Summary
The paper presents scalable, vendor-neutral reference electrical architectures for modern data centers that bridge facility-level design with utility and grid planning. p. 0 This framework integrates modular Power PODs, hierarchical distribution, standby generation, UPS systems, BESS, and utility interfaces into a unified methodology <ref:2611. p. 015712#pg3>.
Core Framework Components
The proposed framework represents the principal functional elements found in modern data-center electrical systems <ref:2611.15712#pg4>. These elements include the utility service interface, HV substations, HV/MV transformers, MV switchgear and feeders, modular power PODs, standby generators, automatic transfer switches (ATSs), uninterruptible power-supply (UPS) systems, battery energy-storage systems (BESSs), and low-voltage (LV) switchboards <ref:2611. p. 115712#pg4>.
Hierarchical Architecture
The architecture follows a hierarchical and modular design that separates electrical infrastructure into HV, MV, and LV layers to preserve a consistent planning representation over a wide range of facility sizes <ref:2611.15712#pg5>. The structure is shown in Figure 1, illustrating the flow from the Utility Transmission Grid through HV Substation(s) to Campus MV Switchgear and then down to Power PODs <ref:2611. p. 115712#pg5>.
Modular Scaling Methodology
The power POD serves as the fundamental modular and repeatable building block of modern data center electrical architectures <ref:2611.15712#pg4>. The methodology allows for consistent capacity expansion by determining the required number of PODs based on target IT capacity and selected POD IT capacity <ref:2611. p. 315712#pg5>. Equipment quantities are then calculated as Nx = qxNpod, where qx is the number of units assigned to each POD for equipment type x <ref:2611. p. 315712#pg5>.
Planning Application and Output
The methodology generates a complete electrical representation by partitioning IT capacity into standardized power PODs and then determining the required campus electrical infrastructure <ref:2611.15712#pg5>. This process involves estimating utility interconnection requirements, equipment demand, and future transmission and distribution planning <ref:2611. p. 115712#pg4>. The final output is a reproducible benchmark for evaluating the impacts of large-scale data center deployment on future power systems <ref:2611. p. 015712#pg4>.
Sample Calculation Illustration
The methodology is illustrated using 100 MW and 500 MW IT facilities with 2.5 MW power PODs and six PODs per data hall <ref:2611. p. 315712#pg5>. For the 500 MW facility, this results in NPOD = PIT/PPOD = 200 and Nhall = NPOD/hall = 34 <ref:2611. p. 315712#pg5>. This scaling demonstrates how POD-level equipment scales with installed IT capacity while upstream infrastructure transitions based on predefined capacity thresholds <ref:2611. p. 415712#pg5>.
Conclusion and Future Direction
The proposed framework successfully combines a hierarchical electrical distribution architecture with modular power PODs and capacity-based planning rules to estimate facility electrical infrastructure <ref:2611.15712#pg4>. The modular and hierarchical architecture enables consistent representation of facilities ranging from tens of megawatts to multi-gigawatt campuses while remaining adaptable to different redundancy philosophies <ref:2611. p. 415712#pg5>. Future work plans to extend the benchmark by incorporating time-varying workload models and detailed dynamic models of on-site energy resources. p. 4
References
[3] U.S. Department of Energy, “2021–2024 Four-Year Review of Supply Chains for the Energy Sector Industrial Base,” U. p. 4 p. 4S. Department of Energy, Washington, DC, USA, Technical Report, Dec. p. 4 p. 4 2024.
[5] North American Electric Reliability Corporation (NERC), “Characteristics and Risks of Emerging Large Loads,” NERC, Atlanta, GA, USA, White Paper, Jul. p. 4 p. 4 2025.
[6] Schneider Electric, “Reference Design 101: 56 MW Tier III Data Center Reference Design,” Schneider Electric, 2024. p. 4 p. 4
[7] Vertiv, “The Data Center Power Train: Managing Energy from Grid to Chip,” Vertiv, Westerville, OH, USA, Mar. p. 4 p. 4 2025.
[8] NVIDIA Corporation, “NVIDIA Contributes NVIDIA GB200 NVL72 Designs to Open Compute Project,” https://developer. p. 4 p. 4nvidia.com/blog/nvidia-contributes-nvidia-gb200-nvl72-designs-to-open-compute-project/, Oct. p. 4 p. 4 2024, nVIDIA Technical Blog, Accessed: Jul. p. 4 p. 4 24, 2026.
[9] Uptime Institute, Tier Standard: Topology, 2018th ed. p. 4 p. 4, Uptime Institute, New York, NY, USA, 2018. p. 4 p. 4
[10] ISO/IEC 22237-1:2021, Information Technology—Data Centre Facilities and Infrastructures—Part 1: General Concepts, International Organization for Standardization and International Electrotechnical Commission Std. p. 4 p. 4, 2021.
[14] Telecommunications Infrastructure Standard for Data Centers, Telecommunications Industry Association Std. p. 4 p. 4 ANSI/TIA-942, 2024. p. 4 p. 4
[15] Schneider Electric, “Ecostruxure data center reference designs,” 2025. p. 4 p. 4
[16] North American Electric Reliability Corporation (NERC), “Reliability Guideline: Risk Mitigation for Emerging Large Loads,” NERC, Atlanta, GA, USA, Reliability Guideline, May 2026. p. 4 p. 4
[17] Schneider Electric, “How 6 AI Attributes Change Data Center Design,” Schneider Electric, White Paper WP110 Version 3. p. 4 p. 41, May 2026. p. 0 p. 0
[18] Vertiv, “Vertiv 360ai high density reference design. p. 4 p. 4027a: 2.5 mw pods at up to 142 kw per rack,” Vertiv, Reference Design, Mar. p. 4 p. 4 2025.
[19] National Fire Protection Association, NFPA 110: Standard for Emergency and Standby Power Systems, National Fire Protection Association Std. p. 4 p. 4 NFPA 110, 2022. p. 4 p. 4
[20] International Electrotechnical Commission, IEC 62040-3:2021 Uninterruptible Power Systems (UPS) – Part 3: Method of Specifying the Performance and Test Requirements, International Electrotechnical Commission Std. p. 4 p. 4 IEC 62 040-3:2021, Apr. p. 4 p. 4 2021.
[21] I. S. 3001.2-2017, Recommended Practice for Evaluating the Electrical Service Requirements of Industrial and Commercial Power Systems, Institute of Electrical and Electronics Engineers Std. p. 4 p. 4, Nov. 2017.
Summary
Scalable reference electrical architectures for modern data centers are presented as a vendor-neutral methodology integrating modular Power PODs with hierarchical distribution to bridge facility design and grid planning <ref:2611.15712#pg4>. This approach provides a reproducible benchmark for estimating electrical infrastructure requirements, equipment demand, and utility interconnection studies across various data center scales <ref:2611. p. 415712#pg4>.
Pruning redundant reasoning tokens
The architecture is generated from four primary inputs summarized in Table I: the facility IT capacity, power POD IT capacity, power usage effectiveness (PUE), and data-center class <ref:2611.15712#pg5>. The PUE relates the IT demand to the total facility demand, and the data-center class determines representative POD capacities and PUE values used by the planning methodology <ref:2611. p. 215712#pg5>. These inputs are sufficient to generate the complete electrical representation, including POD-level equipment, campus electrical infrastructure, and utility interconnection requirements <ref:2611. p. 215712#pg5>.
How the training signal is built
The architecture generation procedure is hierarchical, beginning with partitioning target IT capacity into standardized power PODs to serve as fundamental modular building blocks <ref:2611.15712#pg5>. Each POD contributes a predefined set of electrical equipment, including MV/LV transformers, standby generators, ATSs, UPS modules, battery systems, and power distribution units <ref:2611. p. 315712#pg5>. The process then determines the required number of PODs based on PIT/PPOD to ensure the target IT capacity is met <ref:2611. p. 315712#pg5>.
Where the gains come from
The key gain lies in the ability to translate a small set of facility characteristics into a consistent electrical representation usable for utility interconnection analysis and transmission planning <ref:2611.15712#pg4>. The framework scales with facility size by adding infrastructure at predefined capacity thresholds, ensuring that the same methodology can be consistently applied across different data center types and capacities <ref:2611. p. 415712#pg5>. The resulting equipment requirements originate from the modular powerPOD architecture, providing a scalable and reproducible approach for preliminary infrastructure planning <ref:2611. p. 415712#pg5>.
The sample calculation shows that for a 500 MW facility, NPOD = 200 and Nhall = 34 <ref:2611.15712#pg5>. This calculation illustrates the hierarchical scaling of the reference architecture, showing how POD-level equipment scales with installed IT capacity while upstream infrastructure transitions based on predefined capacity thresholds <ref:2611. p. 415712#pg5>. The final results show that STATCOM requirements are determined independently based on facility apparent-power capacity to represent planning-level grid interface reactive power support <ref:2611. p. 415712#pg5>.
[1] International Energy Agency, “Energy and AI,” IEA, Tech. Rep., 2025.
[2] P. Mitra, “Transmission planning and large data centers,” IEEE Electrification Magazine, vol. p. 4 11, no. 3, pp. 90–92, Sep. p. 4 2023.
[3] U.S. Department of Energy, “2021–2024 Four-Year Review of Supply Chains for the Energy Sector Industrial Base,” U.S. Department of Energy, Washington, DC, USA, Technical Report, Dec. 2024.
[4] Arman Shehabi et al. p. 4, “2024 United States Data Center Energy Usage Report,” Lawrence Berkeley National Laboratory, Berkeley, CA, USA, Tech. p. 4 Rep. LBNL-2001637, Dec. p. 4 2024.
[5] North American Electric Reliability Corporation (NERC), “Characteristics and Risks of Emerging Large Loads,” NERC, Atlanta, GA, USA, White Paper, Jul. 2025.
[6] Schneider Electric, “Reference Design 101: 56 MW Tier III Data Center Reference Design,” Schneider Electric, 2024.
[7] Vertiv, “The Data Center Power Train: Managing Energy from Grid to Chip,” Vertiv, Westerville, OH, USA, Mar. 2025.
[8] NVIDIA Corporation, “NVIDIA Contributes NVIDIA GB200 NVL72 Designs to Open Compute Project,” https://developer.nvidia.com/blog/nvidia-contributes-nvidia-gb200-nvl72-designs-to-open-compute-project/, Oct. 2024, nVIDIA Technical Blog, Accessed: Jul. 24, 2026.
[9] Uptime Institute, Tier Standard: Topology, 2018th ed., Uptime Institute, New York, NY, USA, 2018.
[10] ISO/IEC 22237-1:2021, Information Technology—Data Centre Facilities and Infrastructures—Part 1: General Concepts, International Organization for Standardization and International Electrotechnical Commission Std., 2021.
[11] A. Jimenez-Ruiz and F. p. 4 Milano, “Data center model for transient stability analysis of power systems,” IEEE Transactions on Power Systems, 2025, early Access. p. 4
[12] B. Chalamala, V. p. 4 Rabl et al. p. 4, “Data center growth and grid readiness,” IEEE Power & Energy Society, Technical Report TR131, May 2025. p. 4
[13] B. Chalamala et al. p. 4, “Data centers for future power systems,” IEEE Energy Sustainability Magazine, Tech. p. 4 Rep. 1, Feb. 2026.
[14] Telecommunications Infrastructure Standard for Data Centers, Telecommunications Industry Association Std. ANSI/TIA-942, 2024.
[15] Schneider Electric, “Ecostruxure data center reference designs,” 2025.
[16] North American Electric Reliability Corporation (NERC), “Reliability Guideline: Risk Mitigation for Emerging Large Loads,” NERC, Atlanta, GA, USA, Reliability Guideline, May 2026.
[17] Schneider Electric, “How 6 AI Attributes Change Data Center Design,” Schneider Electric, White Paper WP110 Version 3.1, May 2026.
[18] Vertiv, “Vertiv 360ai high density reference design.027a: 2.5 mw pods at up to 142 kw per rack,” Vertiv, Reference Design, Mar. 2025.
[19] National Fire Protection Association, NFPA 110: Standard for Emergency and Standby Power Systems, National Fire Protection Association Std. NFPA 110, 2022.
[20] International Electrotechnical Commission, IEC 62040-3:2021 Uninterruptible Power Systems (UPS) – Part 3: Method of Specifying the Performance and Test Requirements, International Electrotechnical Commission Std. IEC 62 040-3:2021, Apr. 2021.
[21] I. S. 3001.2-2017, Recommended Practice for Evaluating the Electrical Service Requirements of Industrial and Commercial Power Systems, Institute of Electrical and Electronics Engineers Std., Nov. 2017.
Green — the paper says it, and the page is printed. Red — no passage carries it, so treat that sentence as unverified. The same check runs on your own text: check a summary against its source, $5.
Improvements for AI systems
-
Modular power POD methodology enables consistent capacity expansion by allowing data center operators to scale infrastructure based on predefined modular building blocks rather than bespoke designs. This allows for
consistent capacity expansion and utility interconnection studies.
-
A reproducible planning framework can be used for
evaluating electrical infrastructure requirements, equipment demand, and future transmission and distribution planning associated with large-scale data center deployment.
This provides a benchmark that bridges the gap between facility-level design and grid-level studies. -
The architecture allows for explicit PUE modeling by separating
IT, Cooling, and Auxiliary Loads,
which is particularly important for AI/HPC facilities where these components are tightly integrated. This enables flexibility in modeling cooling technologies against power demands. -
The methodology supports dynamic grid interactions by considering elements like STATCOM sizing based on facility apparent-power capacity to represent
planning-level equipment estimation
for reactive-power support at the grid interface.
Related papers
- Industrial Load Modeling and Optimization for Market-Based Interaction with Power Systems
- Exact and Approximate Convex Reformulation of Linear Stochastic Optimal Control with Chance Constraints
- Certified Set Convergence for Piecewise Affine Systems
- Symbolic Control for Stochastic Systems via Finite Parity Games
- Multiobjective optimization-based design and dispatch of islanded, hybrid microgrids for remote, off-grid communities in sub-Saharan Africa
- Physiology-informed layered sensing for intelligent human-exoskeleton interaction