Transformer-guided Variable Projection for Phasor and Fault-Time Estimation Under DDC Offset

arXiv:2611.03416 · eess.SY, cs.SY · Submitted 2026-11-02 · Read on arXiv

eess.SY, cs.SY

Submitted: 2026-11-02

Updated: 2026-11-02

Comments: 5 pages, 3 figures, 3 tables. Submitted to PESGM

License: http://creativecommons.org/licenses/by/4.0/

The gist: Decaying DC (DDC) offsets introduce substantial phasor estimation errors during the first post-fault cycle.

Terminology

Abstract

Decaying DC (DDC) offsets introduce substantial phasor estimation errors during the first post-fault cycle. Recent approaches have sought interpretable waveform representations, but identifying analytical expressions can incur substantial computational costs. This paper proposes a transformer-guided variable-projection estimator that extracts the fundamental phasor, DDC parameters, and fault inception time from point-on-wave (POW) samples as an interpretable analytical expression. An offline-trained transformer provides the signal structure and decay rate, while variable projection refines the parameters and handles windows containing the fault without knowledge of time of fault. Across single- and dual-DDC scenarios with time constants of 2.5--400 ms, the mean maximum overshoot (MO) is at most 2.7% on post-fault windows and 2.2% during online operation, where the DFT reaches 10--14%. The post-fault phasor settles within 5% approximately 12.5 ms after inception. Circuit-level validation on a 230-kV two-source system yields 1.6% mean MO, compared with 9.5% for the DFT.