Centrality-based Structural-Electrical Contingency Screening and Transmission Reinforcement Prioritization
The study developed a hybrid screening method combining structural analysis (using centrality measures) and flow-based severity assessment (using LODFs) to efficiently evaluate transmission system vulnerabilities from contingencies. This approach creates computationally fast surrogates for complex AC evaluations, providing accurate indices for contingency severity and identifying optimal lines for reinforcement.