Tuning and Testing an Online Feedback Optimization Controller to Provide Curative Distribution Grid Flexibility

summary

The gist

Online Feedback Optimization (OFO) is presented as a new control method that steers power systems to an optimal solution of an optimization problem using minimal model information and computation…

In short

Online Feedback Optimization (OFO) is a control method that uses minimal model information to steer power systems toward an optimal solution for flexibility requests. Experimentally, a tuned OFO controller successfully disaggregates flexibility into Flexible Providing Units (FPUs) while respecting operational constraints. This robust method provides fast flexibility delivery and signals infeasibility when requirements cannot be met.

Key concepts

Online Feedback Optimization (OFO)
A control method that uses real-time feedback from the grid measurements to solve an optimization problem quickly. It aims to find the best way to allocate power flexibility requests among available units using only minimal model data, making it computationally efficient for real-time use.
Constraint Approach vs. Cost Approach
Two ways to define the mathematical optimization problem for finding FPU setpoints. The constraint approach was found superior because it leads to lower grid losses and is more versatile, allowing the cost function to be tuned for desired system behavior, unlike the cost approach which converges slowly when constraints are active.
Projected Gradient Descent (PGD)
The underlying mathematical structure of the OFO controller. It uses an integral controller combined with a Quadratic Programming (QP) problem. The tuning matrix G adjusts the convergence speed of this process, where smaller values in G accelerate convergence by weighting specific variables more heavily.

Terminology used across episodes

This episode discusses

The paper

Tuning and Testing an Online Feedback Optimization Controller to Provide Curative Distribution Grid Flexibility · Read on arXiv

Lukas Ortmann, Saverio Bolognani, Florian Dorfler, Fabian Bohm, Florian Klein-Helmkamp, Andreas Ulbig

Automatic Control Laboratory at ETH Zurich, Switzerland · IAEW at RWTH Aachen

Due to more volatile generation, flexibility will become more important in transmission grids. One potential source of this flexibility can be distribution grids. A flexibility request from the transmission grid to a distribution grid then needs to be split up onto the different flexibility providing units (FPU) in the distribution grid. One potential way to do this is Online Feedback Optimization (OFO). OFO is a new control method that steers power systems to the optimal solution of an optimization problem using minimal model information and computation power. This paper will show how to choose the optimization problem and how to tune the OFO controller. Afterward, we test the resulting controller on a real distribution grid laboratory and show its performance, its interaction with other controllers in the grid, and how it copes with disturbances. Overall, the paper makes a clear recommendation on how to phrase the optimization problem and tune the OFO controller. Furthermore, it experimentally verifies that an OFO controller is a powerful tool to disaggregate flexibility requests onto FPUs while satisfying operational constraints inside the flexibility providing distribution grid.

DOI: 10.1016/j.epsr.2024.110660

Transcript

Introduction to the show: ident: Robotics Radio. Generated commentary on the latest robotics and control papers.

Rosa: We're looking at the paper: "Tuning and Testing an Online Feedback Optimization Controller to Provide Curative Distribution Grid Flexibility".

Dev: Here's the gist of the paper. Online Feedback Optimization (OFO) is presented as a new control method that steers power systems to an optimal solution of an optimization problem using minimal model information and computation power.

Rosa: This paper experimentally verifies that an OFO controller is a powerful tool to disaggregate flexibility requests onto FPUs while satisfying operational constraints inside the flexibility providing distribution grid.

Dev: Problem Definition and Methodology The core task involves defining an optimization problem whose solution provides setpoints to the Flexibility Providing Units (FPUs).

Rosa: The authors compare two fundamentally different ways to define this optimization problem and give a clear recommendation on which formulation is superior.

Title and authors: Rosa: Now that we know what it is about, let’s look at the specifics of what this paper, "Tuning and Testing an Online Feedback Optimization Controller to Provide Curative Distribution Grid Flexibility," actually does. They compare two ways to define the optimization problem: a cost approach and a constraint approach.

Dev: That comparison is important because they actually recommend the constraint approach because it leads to lower losses in the grid, which is a big deal for efficiency, and it's more versatile because you can use its cost function to parameterize certain behaviors.

Taro: I’m curious about that constraint approach part since I worry about how fast things settle; does it actually converge quickly when constraints become active?

Rosa: It does, and they found that the constraint approach achieves nearly immediate convergence, whereas the cost approach can show extremely slow convergence when those constraints kick in.

Dev: So one of the key takeaways from this paper is that the constraint approach is superior because it handles feasibility better and results in less grid loss compared to what their cost approach produces.

Taro: It sounds like they’ve found a way to make sure that when the system needs help, it finds a solution quickly without wasting time getting stuck in slow convergence issues.

The paper's summary: Rosa: Moving on to what this paper actually summarizes, they describe the OFO controller dynamic system as an update of the total derivative of an objective function based on voltage measurements and power flows.

Dev: They’re using an integrator with a constant sigma to update that objective function, and then they solve a quadratic problem inside that loop to find the next set points for active and reactive power.

Taro: The paper details how they define the terms like the gradient of the objective function, which is approximated by something called H sub p and H sub v, based on how changes in power flow affect voltages.

Rosa: They calculate these terms using sensitivities like the partial derivatives of active and reactive power with respect to power flow and disturbances, and they approximate them as constant vectors or matrices for simplicity.

Dev: The whole point of this setup is that the OFO controller iteratively changes those set points until it reaches a solution for that underlying optimization problem, which is what drives the control loop.

Taro: It sounds like they are using these gradient approximations to guide the system toward an optimal state without needing a full, complex model for every tiny change in the grid.

The paper's improvements: Rosa: Now for what they suggest as improvements, they focus on how this method can be made more robust and better suited for real-world operation. They show that the tuned OFO controller is compatible with other control devices already present in the grid.

Dev: They tested it on a distribution grid laboratory at RWTH Aachen University to prove its behavior in a real grid, and they showed that this tuned controller can deliver the requested flexibility fast while still guaranteeing operational limits.

Taro: What I like is that they show it’s robust to model mismatch and changing consumption or production in the distribution grid, meaning it uses feedback from measurements instead of just relying on static models.

Rosa: And they also tested its interaction with other devices, like an inverter doing voltage control according to VDE4105, and the controller successfully mitigates small voltage violations within one sampling interval when talking to an independent photovoltaic inverter.

Dev: They also showed that the constraint approach signals infeasibility if the requested flexibility just can't be provided by the grid, which is a necessary check for safety.

Conclusion: Rosa: So, wrapping up on "Tuning and Testing an Online Feedback Optimization Controller to Provide Curative Distribution Grid Flexibility," the paper shows that OFO with the constraint approach is a powerful way to disaggregate flexibility requests onto FPUs in a distribution grid.

Dev: It provides the requested flexibility and it signals impossibility if the grid genuinely cannot provide it, which is a solid safety feature. The tuning makes sure it’s robust to changes in consumption and production while using all of the available flexibility.

Taro: I think the main implication for me is that having a system that can handle those real-world disturbances without needing perfect models is crucial for any autonomous system operating in a grid environment.

Rosa: And it's also compatible with other control devices, meaning you can actually plug this into an existing infrastructure and get fast delivery of flexibility while respecting all operational limits.

Dev: It’s a solid tool for managing that distributed flexibility, and the constraint approach is the better way to go based on their testing results.

Taro: We're looking forward to seeing how this kind of feedback-based optimization gets applied when you try to scale this up to much larger networks or more complex scenarios.